1 Scope
This document provides a test procedure for evaluating the performance of Over Voltage
Ride-Through (OVRT) functions in inverters used in utility-interconnected photovoltaic (PV) systems.
This document is most applicable to large systems where PVinverters are connected
to utility high voltage (HV) distribution systems. However, the applicable procedures
may also be used for low voltage (LV) installations in locations where evolving OVRT requirements include such installations, e.g. single-phase or 3-phase systems.
Fundamentally, the assessed OVRT performance is valid only for the specific configuration and operational mode of
the inverter under test. Separate assessment is required for the inverter in other factory or user-settable configurations, as these may cause the inverterOVRT
response to behave differently.
The measurement procedures are designed to be as non-site-specific as possible, so
that OVRT characteristics measured at one test site, for example, can also be considered valid
at other sites.
This document is for testing of PVinverters, though it contains information that may
also be useful for testing of a complete PV power plant consisting of multiple inverters connected at a single point to the utility grid. It further provides a basis for utility-interconnected PVinverters numerical simulation
and model validation.