Thermostatic mixing valves for use in care establishments. Requirements and test methods

Thermostatic mixing valves for use in care establishments. Requirements and test methods

Regular price
£322.00
Sale price
£322.00
Regular price
£161.00
Sold out
Unit price
per 

1   Scope

This British Standard specifies performance and material requirements and gives test methods for three types of TMV, of nominal size up to and including DN25, for use in care establishments. The TMVs covered by this standard are those which are suitable for the hot and cold water supply pressures and temperatures given in Table 1, and those which are suitable for the applications given in Table 2.
Annex A to Annex E give the apparatus and test methods for the durability of TMVs, Annex F to Annex M and Annex O to Annex S give the apparatus and test methods for the performance of TMVs. Annex N gives an assessment of transient values, Annex T gives a summary of thermal performance requirements and Annex U and Annex V give recommendations for commissioning and in-service tests.
Table 1TMV general use conditions
Pressure/temperature range High pressure (HP) Low pressure (LP)
Operating pressure    
 Maximum static water pressure (MPa) 1.0 1.0
 Flow pressure, hot and cold (MPa) 0.1 to 0.5 0.02 to 0.1
Operating temperature    
 Hot supply temperature (°C) 55 to 65 55 to 65
 Cold supply temperature (°C) 5 to 20 5 to 20
Table 2Mixed-water temperature
Application Designation A) Mixed-water temperature (at point of discharge)°C max.
Bidet HP-B, BE; LP-B, BE 38
Shower HP-S, SE; LP-S, SE 41
Washbasin HP-W, WE; LP-W, WE 41
Bath (44 °C fill) HP-T44; LP-T44 44
Bath (46 °C fill) HP-T46; LP-T46 46
Bath and shower mixer (44 °C bath fill) HP-D44; LP-D44 41 (shower);
    44 (bath)
Bath and shower mixer (46 °C bath fill) HP-D46; LP-D46 41 (shower);
    46 (bath)

NOTE For washbasins, washing is assumed to take place under running water.

A) A TMV with a diverter designation (D) has the capability to change and control the mixed-water outlet temperature in line with the temperatures defined above when the supply path is changed from bath to shower or shower to bath.