1 Scope
This clause of part 1 applies except as follows.
Replacement:
This standard applies to electronic switches and to associated electronic extension units for household and similar fixed electrical installations either indoors or outdoors.
It applies to electronic switches for a.c. only, for the operation of lamp circuits
and the control of the brightness of lamps (dimmers) as well as the control of the
speed of motors (for example, those used in ventilating fans) and for other purposes
(for example, heating controls), with a rated voltage not exceeding 250 V and a rated
current not exceeding 16 A.
The operation and/or control as mentioned above are performed by a person via an actuating member, a sensing surface or a sensing
unit, by means of touch, proximity, turn, optical, acoustic, thermal or any other
influence.
This standard also applies to general purpose electronic switches with included automatic
functions where the operation and/or the control is initiated by a change of a physical
quantity, for example light, temperature, humidity, time, wind velocity, presence
of persons, etc.
This standard also applies to boxes for electronic switches, with the exception of
mounting boxes for flush-type electronic switches.
This standard also applies to electronic RCS and electronic TDS with a rated voltage not exceeding 440 V and a rated current not exceeding 25 A,
intended for household and similar fixed electrical installations, either indoors
or outdoors.
NOTE 1 Switches including only passive components such as resistors, capacitors, inductors,
PTC and NTC components, varistors, printed wiring boards and connectors are not considered
as electronic switches.
NOTE 2 Electronic switches may have control circuits with a.c. or d.c. rated control voltages.
Electronic switches complying with this standard are suitable for use at ambient temperature
not normally exceeding 25 °C but occasionally reaching 35 °C.
In locations where special conditions prevail, such as in ships, vehicles and the
like and in hazardous locations, for example, where explosions are liable to occur,
special constructions may be required.
NOTE 3 This standard is not intended to cover devices which are designed to be incorporated
in appliances or are intended to be delivered together with a specific appliance and
which are within the scope of IEC 60730 or IEC 61058‑1.
Examples of designs of electronic switches and functions are shown in annex AA.
NOTE 4 Electronic switches without a mechanical switch in the main circuit do not provide
a “full off-state”. Therefore, the circuit on the load side should be considered to
be live.