1   Scope

This part of ISO 4126 specifies the sizing of safety valves for gas/liquid two-phase flow in pressurized systems such as reactors, storage tanks, columns, heat exchangers, piping systems or transportation tanks/containers. The possible fluid states at the safety valve inlet that can result in two-phase flow are given in Table 1.

NOTE The expression “safety valve” is a synonym for valves as described in ISO 4126‑1, ISO 4126‑4 and ISO 4126‑5.

Table 1Possible fluid state at the inlet of the safety valve that can result in two-phase flow
Fluid state at valve inlet Cases Examples
liquid subcooled (possibly flashing in the safety valve)
saturated
with dissolved gas
cold water
boiling water
CO2/water
gas/vapour near saturated vapour (possibly condensing in the safety valve) steam
gas/liquid vapour/liquid
non-evaporating liquid and non-condensable gas (constant quality)
gas/liquid mixture, when gas is desorbed or produced
steam/water
air/water