1 Scope
-
• have a rated powerPN from 0,12 kW to 1 000 kW;
-
• have a rated voltage UN above 50 V up to 1 kV;
-
• have a rated speednN from 600 1/min up to 6 000 1/min regardless of the number of magnetic poles;
-
• are designed for cooling methods IC4A1A0 (IC410), IC4A1A1 (IC411), IC4A1A6 (IC416), or IC4A1A8 (IC418) according to IEC 60034‑6;
-
• are capable of continuous operation at their rated operating point (torque/power, speed) with a temperature rise within the specified insulation temperature class;
NOTE 1 Most motors covered by this document are rated for duty type S1 (continuous duty). However, some motors that are rated for other duty cycles are still capable of continuous operation at their rated power and these motors are also covered. Motors rated between S3 and S10 with a cycle time of 80 % or more may be included.
-
• are rated for any ambient temperature within the range of – 20 °C to + 60 °C;
NOTE 2 The rated efficiency and efficiency classes are based on 25 °C ambient temperature according to IEC 60034‑2‑1 and IEC TS 60034‑2‑3.
NOTE 3 Motors rated for temperatures outside the range – 20 °C and + 60 °C are considered to be of special construction and are consequently excluded from this document.
NOTE 4 Smoke extraction motors with a temperature class of up to and including 400 °C are covered by this document.
-
• are rated for an operating altitude up to 4 000 m above sea level.
NOTE 5 The rated efficiency and efficiency class are based on a rating for altitudes up to 1 000 m above sea level.
-
• Motors with flanges, feet and/or shafts with mechanical dimensions different from IEC 60072‑1.
-
• Geared motors including those incorporating non-standard shafts and flanges. However, the testing of efficiency is to be performed on the motor part of a geared motor only.
-
• Motors specifically built for operation in explosive environments according to IEC 60079‑0. Such motors may not be able to reach the higher efficiency classes (due to safety requirements and possible design constraints of explosion proof motors such as increased air-gap, reduced starting current, enhanced sealing).
-
• Motors with mechanical commutators;
-
• Motors completely integrated with the driven machine (for example pumps, fans and compressors) that cannot be practically tested separately from the machine even with provision of a temporary end-shield and drive-end bearing. This means that motors included in this document must:
-
a) share common components (apart from connectors such as bolts) with the driven unit (for example, a shaft or housing), and
-
b) not be designed in such a way as to enable the motor to be separated from the driven unit as an entire motor that can operate independently of the driven unit, When the process of separation renders the motor inoperative, it is excluded from this document.
-
NOTE 6 Some motors used in horizontal, inclined and vertical transport of goods and people are specifically designed for this purpose. They are often integrated into a machine and are not brought to the market as individual products. These motors are excluded.
-
• Brake motors when the brake is an integral part of the inner motor construction and can neither be removed nor supplied by a separate power source during the testing of motor efficiency.Brake motors with a brake coil that is integrated into the flange of the motor are covered as long as it is possible to test motor efficiency without the losses of the brake (for example by dismantling the brake, removing the brake or by energizing the brake coil from a separate power source).
-
• Submersible motors specifically designed to operate wholly immersed in a liquid;
-
• Smoke extraction motors with a temperature class above 400 °C;
-
• Motors that are just soft-started with a frequency-converter and then operated on sinusoidal mains supply are rated according to IEC 60034‑30‑1;
-
• Motors that are designed for servo applications, i.e. applications where frequent overload or field-weakening operations or frequent speed or torque changes occur or no thermal steady state operation is reached.
NOTE 7 This document covers industrial motors which mostly run continuously at or near rated load, and whose speed is not changing often or rapidly. Such motors include those which drive compressors and conveyor belts, for example.