1 Scope
This part of IEC 62672 applies to all line-commutated high-voltage direct current (HVDC) transmission systems
used for power exchange in utility systems. HVDC stations with voltage sourced converters
(VSC) are not covered.
In order to assess the operational performance of HVDC transmission systems, reliability
and availability need to be evaluated. For this purpose the HVDC users/owners are
encouraged to compile reports on an annual basis based on the recommendations given
in this Technical Specification. The purpose of this part of IEC 62672 is to define a standardized reporting protocol so that data collected from different
HVDC transmission systems can be compared on an equitable basis. It is recommended
that such reports are sent to Cigré SC B4, “HVDC and Power Electronics” (http://b4.cigre.org) who collects such data and publishes a survey of HVDC systems throughout the world
on a bi-annual basis.
This part of IEC 62672 covers point-to-point transmission systems, back-to-back interconnections and multi-terminal
transmission systems. For point-to-point systems and back-to-back interconnections,
i.e. two-terminal systems, statistics are to be reported based on the total transmission
capability from the sending end to the receiving end measured at a given point. If,
however, the two terminals are operated by different users/owners, or are composed
of equipment of different vintage or of equipment from different suppliers, statistics
can be reported on an individual station basis if so desired by those responsible
for reporting. In such a case, the outage should only be reported under the originating converter station taking care not to
report the same event twice. For distributed multi-terminal systems, i.e. systems
with more than two terminals, statistics are to be reported separately for each converter
station based on its own individual capability.
Multi-terminal systems, incorporating parallel converters but having only two converter
stations on the d.c. line, can be considered as either point-to-point systems or as
multi-terminal systems for purpose of reporting. Therefore, statistics for this special
type of multi-terminal system can be reported based on either total transmission capability
or on individual station capability. If the converters at one station use different
technology, converter station statistics can be reported separately for each different
type of capacity if desired. Multiple bipoles are also to be reported individually.
Special mention should be given in the text and in the tabulations to any common events
resulting in bipolar outages.
NOTE Usually the agreement between the purchaser and the turnkey suppliers of the HVDC converter station includes specific requirements regarding contractual evaluation. Such specific requirements will govern over this Technical Specification.