1 Scope
This document specifies requirements for devices for the suppression of DC magnetic
bias of power transformers and convertor transformers. It includes requirements for
service conditions, structures, testing, packing, transport and storage.
The devices are connected to neutral points of power transformers and converter transformers
to suppress DC bias current in the case an HVDC system is operated in monopole ground return mode or bipolar
unbalanced mode. In the case of dedicated metallic return HVDC system, the devices
are useful to mitigate DC stray current flowing through power transformers and converter
transformers during transient conditions such as DC line fault.
This document applies to DC magnetic bias suppression devices for operation at frequencies of 50 Hz and 60 Hz on power systems having voltages
above 110 kV.