1 Scope
This part of IEC 60919 provides general guidance on the steady-state performance requirements of high-voltage
direct current (HVDC) systems. It concerns the steady-state performance of two-terminal
HVDC systems utilizing 12-pulse converter units comprised of three-phase bridge (double-way)
connections (see Figure 1), but it does not cover multi-terminal HVDC transmission systems. Both terminals
are assumed to use thyristor valves as the main semiconductor valves and to have power
flow capability in both directions. Diode valves are not considered in this document.
Only line-commutated converters are covered in this document, which includes capacitor
commutated converter circuit configurations. General aspects of semiconductor line-commutated
converters are given in IEC 60146‑1‑1, IEC TR 60146‑1‑2 and IEC 60146‑1‑3. Voltage-sourced converters are not considered.
The distinction is made between system performance specifications and equipment design
specifications for individual components of a system. Equipment specifications and
testing requirements are not defined in this document. Also excluded from this document
are detailed seismic performance requirements. In addition, because there are many
variations between different possible HVDC systems, this document does not consider
these in detail; consequently, it is not used directly as a specification for a particular
project, but rather to provide the basis for an appropriate specification tailored
to fit actual system requirements.
This document, which covers steady-state performance, is followed by the additional
documents of IEC TR 60919‑2 on faults and switching as well as IEC TR 60919‑3 on dynamic conditions. All three aspects are considered when preparing two-terminal
HVDC system specifications.