1 Scope
This part of IEC 60919 which is a technical report provides guidance on the transient performance and fault
protection requirements of high voltage direct current (HVDC) systems. It concerns
the transient performance related to faults and switching for two-terminal HVDC systems
utilizing 12-pulse converter units comprised of three-phase bridge (double way) connections
but it does not cover multi-terminal HVDC transmission systems. However, certain aspects
of parallel converters and parallel lines, if part of a two-terminal system, are discussed.
The converters are assumed to use thyristor valves as the bridge arms, with gapless
metal oxide arresters for insulation co-ordination and to have power flow capability
in both directions. Diode valves are not considered in this report.
Only line-commutated converters are covered in this report, which includes capacitor
commutated converter circuit configurations. General requirements for semiconductor
line-commutated converters are given in IEC 60146‑1‑1, IEC 60146‑1‑2 and IEC 60146‑1‑3. Voltage-sourced converters are not considered.
The report is comprised of three parts. IEC 60919‑2, which covers transient performance, will be accompanied by companion documents,
IEC 60919‑1 for steady-state performance and IEC 60919‑3 for dynamic performance. An effort has been made to avoid duplication in the three
parts. Consequently users of this report are urged to consider all three parts when
preparing a specification for purchase of a two-terminal HVDC system.
Readers are cautioned to be aware of the difference between system performance specifications
and equipment design specifications for individual components of a system. While equipment
specifications and testing requirements are not defined herein, attention is drawn
to those which could affect performance specifications for a system. Note that detailed
seismic performance requirements are excluded from this technical report. In addition,
because of the many possible variations between different HVDC systems, these are
not considered in detail. Consequently this report should not be used directly as
a specification for a specific project, but rather to provide the basis for an appropriate
specification tailored to fit actual system requirements for a particular electric
power transmission scheme. This report does not intend to discriminate the responsibility
of users and manufacturers for the work specified.
Terms and definitions for high-voltage direct current (HVDC) transmission used in
this report are given in IEC 60633.
Since the equipment items are usually separately specified and purchased, the HVDC
transmission line, earth electrode line and earth electrode are included only because
of their influence on the HVDC system performance.
For the purpose of this report, an HVDC substation is assumed to consist of one or
more converter units installed in a single location together with buildings, reactors,
filters, reactive power supply, control, monitoring, protective, measuring and auxiliary
equipment. While there is no discussion of a.c. switching substations in this report,
a.c. filters and reactive power sources are included, although they may be connected
to an a.c. bus separate from the HVDC substation.