1 Scope
This International Standard deals with the techniques for sampling free gases from
gascollecting relays from power transformers. Three methods of sampling free gases
are described.
The techniques for sampling oil from oil-filled equipment such as power and instrument
transformers, reactors, bushings, oil-filled cables and oil-filled tank-type capacitors
are no longer covered by this standard, but are instead described in 4.2 of IEC 60475:2011.
Before analysing the gases dissolved in oil, they are first extracted from the oil.
Three basic methods are described, one using extraction by vacuum (Toepler and partial
degassing), another by displacement of the dissolved gases by bubbling the carrier
gas through the oil sample (stripping) and the last one by partition of gases between
the oil sample and a small volume of the carrier gas (headspace). The gases are analysed
quantitatively after extraction by gas chromatography; a method of analysis is described.
Free gases from gas-collecting relays are analysed without preliminary treatment.
The preferred method for assuring the performance of the gas extraction and analysis
equipment, considered together as a single system, is to degas samples of oil prepared
in the laboratory and containing known concentrations of gases (“gas-in-oil standards”)
and quantitatively analyse the gases extracted. Two methods of preparing gas-in-oil
standards are described.
For daily calibration checks of the chromatograph, it is convenient to use a standard
gas mixture containing a suitable known amount of each of the gas components to be
in a similar ratio to the common ratios of the gases extracted from transformer oils.
The techniques described take account, on the one hand, of the problems peculiar to
analyses associated with acceptance testing in the factory, where gas contents of
oil are generally very low and, on the other hand, of the problems imposed by monitoring
equipment in the field, where transport of samples may be by un-pressurized air freight
and where considerable differences in ambient temperature may exist between the plant
and the examining laboratory.