1 Scope
This International Standard specifies oil-sampling procedures, analysis requirements
and procedures, and recommends sensitivity, repeatability and accuracy criteria for
the application of dissolved gas analysis (DGA) to factory testing of new power transformers,
reactors and instrument transformers filled with mineral insulating oil when DGA testing
has been specified.
The most effective and useful application of DGA techniques to factory testing is
during the performance of long-term tests, typically temperature-rise (heat run) and
overloading tests on power transformers and reactors, also impulse tests on instrument
transformers. DGA may also be valuable for over-excitation tests run over an extended
period of time.
Experience with DGA results, before and after short-time dielectric tests, indicates
that DGA is normally less sensitive than electrical and acoustic methods for detecting
partial discharges. However, DGA will indicate when these partial discharges become
harmful to the insulation and may be detected by inspection [2].