1 Scope
This document deals with the likely degradation of air performance of fans tested
in standardized airways according to ISO 5801 when compared with the performance of fans tested under actual site conditions. It
deals with the performance of a number of generic types of fan and fittings. The results
given are intended as guidelines and only provide trends, as the system effect depends
on the exact geometry of the fan and disturbing component.
The test data presented in this document are taken from an extensive experimental
program conducted 20 years ago by NEL (National Engineering Laboratory, UK), mainly
on axial and centrifugal fans. Data are also taken from several research projects
financially supported by ASHRAE, some of them being carried out in the AMCA laboratory
in Chicago, as well as from results published previously by individual fan manufacturers.