1 Scope
This Technical Specification specifies the construction, testing, installation and
maintenance of Power-i apparatus and systems which utilise electronically controlled
spark duration limitation to maintain an adequate level of intrinsic safety.
This Technical Specification contains requirements for intrinsically safe apparatus
and wiring intended for use in explosive atmospheres and for associated apparatus
intended for connection to intrinsically safe circuits entering such atmospheres.
This Technical Specification excludes the level of protection “ia” and the use of
software-controlled circuits.
This Technical Specification applies to electrical equipment utilising voltages not
higher than 40 V d.c. and a safety factor 1,5 for Groups IIB, IIA, I and III. It is
also applicable to Group IIC “ic” apparatus with a safety factor 1,0. Group IIC “ib”
apparatus with a safety factor 1,5 are restricted to voltages up to 32 V d.c.
This type of protection is applicable to electrical equipment in which the electrical
circuits themselves are incapable of causing an explosion of the surrounding explosive
atmospheres.
This Technical Specification is applicable to intrinsically safe apparatus and systems
which utilise electronically controlled spark duration limitation with the aim of
providing more electrical power while maintaining an adequate level of safety.
This Technical Specification is also applicable to electrical equipment or parts of
electrical equipment located outside hazardous areas or protected by another type
of protection listed in the IEC 60079 series, where the intrinsic safety of the electrical circuits in explosive atmospheres
depends on the design and construction of such electrical equipment or parts of such
electrical equipment. The electrical circuits located in the hazardous area are evaluated
for use in such locations by applying this Technical Specification.
This Technical Specification supplements and modifies the requirements of IEC 60079‑0, IEC 60079‑11, IEC 60079‑14, IEC 60079‑17 and IEC 60079‑25.