1 Scope
This European Standard is applicable to detection and measurement apparatus and systems
for flammable or toxic gases or vapours or oxygen. It covers apparatus intended to
measure reliably, gas concentration and to provide an output signal (alarm and/or
measurement signal), the purpose of which is to give a warning of a potential hazard.
This European Standard is a product standard which is based on EN 61508 (all parts) and for gas detection systems covers both low and high demand mode at SIL capabilities
of 1, 2 or 3 only. Gas detection apparatus and gas detection systems are developed
as generic products. This European Standard covers part of the phase 10 “realization”
of the overall safety lifecycle defined in EN 61508‑1:2010, Figure 2. Configuration and integration into specific applications is not covered by this
European Standard.
In the event of conflict between the requirements of this European Standard and those
of EN 61508, EN 50402 will take precedence.
NOTE 1 Applications requiring a SIL capability of 4 for a gas detection system are not practicable.
This European Standard is dedicated mainly to fixed apparatus and systems. However,
it can also be applied to transportable gas detectors which are intended to be used
as temporary replacements for fixed apparatus.
This European Standard supplements the requirements of the European Standards for
electrical apparatus for the detection and measurement of flammable gases, vapours
(e.g. EN 60079‑29‑1 or EN 60079‑29‑4), toxic gases (e.g. EN 45544) or oxygen (e.g. EN 50104).
NOTE 2 These European Standards are called in the text “metrological standards”.
The examples above show the state of the standardization for industrial applications
at the time of publishing this European Standard. There may be other metrological
standards covering other application fields, for which this European Standard is also
applicable.
EN 50271
specifies minimum requirements for apparatus using software and/or digital components. It also defines additional optional requirements for compliance with SIL 1 in low
demand mode operation. EN 50402 includes all requirements of EN 50271.
EN 50402
is also dedicated to apparatus and gas detection systems and/or components and should be used instead of EN 50271 in the following cases:
-
— at SIL 1 when the system contains components not covered by EN 50271;
-
— at SIL 1 high demand mode operation;
-
— at SIL 2 and SIL 3;
-
— at all SILs when non-digital based apparatus is used.
Applying the above-mentioned metrological standards will ensure the performance is
adequate in normal operation of a gas detection system. Additionally, the requirements
of this European Standard address the functional safety of gas detection systems and encompass criteria for reliability, fault tolerance and avoidance of systematic failures. The avoidance and control of systematic
failures will be covered by the requirements for the development processes and techniques
and diagnostic measures chosen in the design. This European Standard will lead to
the characterization of the gas detection system by a SIL-capability and related hardware
failure rate representing a hierarchical order of safety levels. This will allow the
user to incorporate the gas detection system into an overall safety system according
to the safety integrity levels of EN 61508 (all parts).
This European Standard is applicable for gas detection systems, which may consist
of the following functional units:
-
— gas-sampling;
-
— sensor;
-
— signal transmission;
-
— input to control unit;
-
— signal processing in control unit;
-
— output from control unit.
This European Standard does not specify requirements for the installation and maintenance
of gas detection systems. It also does not specify the physical positioning of measuring points / locations.
This European Standard does not specify which SIL-capability is sufficient for which
application.
NOTE 3 The SIL-capability required for an application will be specified by the user (see Clause 9 and Annex A).