1 Scope
This Part of IEC 61378 deals with the specification, design and testing of power transformers and reactors
which are intended for integration within semiconductor converter plants; it is not
applicable to transformers designed for industrial or public distribution of a.c.
power in general.
The scope of this International Standard is limited to application of power converters
of any power rating. Typical applications are: thyristor rectifiers for electrolysis;
diode rectifiers for electrolysis; thyristor rectifiers for large drives; thyristor
rectifiers for scrap melting furnaces, and diode rectifiers feeding inverters for
variable speed drives. The standard also covers the regulating unit utilized in such
application as step down regulating transformers or autotransformers. The valve winding
highest voltage for equipment is limited to 36 kV.
This standard is not applicable to transformers for HVDC power transmission. These
are high-voltage transformers, and they are subjected to d.c. voltage tests.
The standards for the complete converter plant (IEC 60146 series, or other publications dedicated to particular fields of application) may
contain requirements of guarantees and tests (such as insulation and power loss) for
the whole plant, including the converter transformer and possibly auxiliary transformers
and reactor equipment. This does not relieve the application of the requirements of
this standard concerning the guarantees and tests applicable to the converter transformer
itself as a separate component before being assembled with the remainder of the converter
plant.
The guarantees, service and type tests defined in this standard apply equally to transformers
supplied as part of an overall converter package, or to those transformers ordered
separately but for use with converter equipment. Any supplementary guarantee or special
verification has to be specifically agreed in the transformer contract.
The converter transformers covered by this standard may be of the oil-immersed or
dry-type design. Unless specific exceptions are stated in this standard, the transformers
comply with IEC 60076 series for oil-immersed transformers, and with IEC 60076‑11 for dry-type transformers.
NOTE For some converter applications, it is possible to use common distribution transformers of standard design. The use of such standard transformers in the special converter applications may require a certain derating. This matter is not specifically covered in this standard, which deals with the requirements to be placed on specially designed units. It is possible to estimate this derating from the formulae given in 5.1, and also from clause 9 of IEC 60076‑8:1997.
This standard deals with transformers with one or more active parts installed in the
same tank like regulating (auto)transformer and one or two rectifier transformers.
It also covers transformers with transductors and/or one or more interphase transformers.
For any combination not listed above an agreement between the purchaser and manufacturer
is necessary regarding the determination and the measurement of the total losses.
This standard deals with transformers star Y and delta D and any other phase shifting
connections (like zig-zag, extended delta, polygon etc.). Phase shifting windings
can be placed on either the regulating or rectifier transformer.