1 Scope
This European Standard specifies requirements, methods of test and performance criteria
against which the compatibility of components and their performance can be assessed
when used in combination to form an electrically controlled hold-open system. It also
specifies requirements for the integrity of such hold-open systems when connected
to fire detection and fire alarm systems or other systems, including the signal exchange and technical data for interfaces.
This European Standard provides requirements for the application of electrically controlled
hold-open systems used for fire/smoke doors in buildings, where such doors are required
to be self-closing. It covers planning, design (see Annex A), installation (see Annex B), commissioning, use and maintenance (see Annex E) of hold-open systems, intended for the protection of life and/or the protection
of property. This may also include hold-open systems, or components of the hold-open
system, that are self-contained in a single enclosure.
Electrically controlled hold-open systems manufactured, installed and serviced in
accordance with this European Standard are recommended for use wherever there is a
requirement for reliable hold-open and release of an individual self-closing fire/smoke
door assembly in the case of fire.
The use of hold-open systems for closures in conveyor systems conforming to EN 1366‑7, which applies in conjunction with EN 1363‑1, may require additional proof of suitability, which is not covered by this European
Standard.
This European Standard does not cover design, installation, commissioning, use and
maintenance of building fire detection and fire alarm systems (covered by CEN/TS 54‑14) but does cover the connection of hold-open systems conforming to this European Standard
to building fire detection and fire alarm systems, under certain prescribed conditions.
This European Standard does not cover the requirements of performance characteristics
and operational environment conditions of particular components of a hold-open system,
where these requirements are already covered by European specifications, and which
include appropriate test methods to assure reproducible test results for the product
conformity assessment. These European Standards are referred to in Clause 5.
This European Standard does not cover electrically controlled systems used for smoke
venting purposes or systems that allow the door to remain open under fault conditions
(i.e. not fail-safe).
This European Standard does not cover electrically controlled hold-open systems that
are not connected to main power supply and are battery powered only.