1 Scope
This standard specifies the requirements, performance criteria and testing procedures
for control and indicating equipment (CIE) intended for use in intrusion and hold-up alarm systems (I&HAS) installed in buildings. This document also applies
to CIE to be used in IAS or HAS.
The CIE may incorporate processing functions of other I&HAS components or its processing
requirements may be distributed among such components.
This standard specifies the requirements for CIE installed in buildings using specific
or non-specific wired interconnections or wire-free interconnections. These requirements
also apply to ACE that are installed inside or outside of the supervised premises
and mounted in indoor or outdoor environments.
Where CIE shares means of detection, interconnection, control, communication, processing
and/or power supplies with other applications, these requirements apply to I&HAS functions
only.
This standard specifies performance requirements for CIE at each of the four security
grades identified in the European Standard EN 50131‑1, “Alarm Systems – Intrusion and hold-up systems – System requirements”. Requirements are also specified for four environmental classes covering applications
for indoor and outdoor locations.
This standard includes mandatory functions, which shall be provided on all CIE for
the appropriate security grade, as well as optional functions that may additionally
be provided.
This standard does not deal with requirements for compliance with EU regulatory Directives,
such as the EMC Directive, Low Voltage Directive, etc. except in that it specifies
the equipment operating conditions for EMC susceptibility testing as required by EN 50130‑4.
NOTE In this standard reference to the term “I&HAS” is used throughout, except where there is specific need to differentiate between the IAS and HAS portions of a system. The term is intended to include IAS and HAS when such systems are installed separately.